A motor control center (MCC) is a factory-assembled switchgear and controlgear assembly housing multiple motor feeder units — each combining an isolator, a contactor or circuit breaker, overload protection, and control wiring — within a common enclosure fed from a shared busbar, used to start, protect, and control groups of electric motors in industrial and utility plants. This guide walks through the first-principles calculations an engineer needs before specifying an MCC: full-load current (FLC), starting current, short-circuit withstand, and busbar sizing with diversity, followed by selection criteria and the governing IEC standards. The guidance applies equally to projects across the Middle East and Gulf (including Egypt and Saudi Arabia), North Africa, the CIS region, and Sub-Saharan Africa, where ambient temperature, dust ingress, and grid fault levels strongly influence MCC design margins.

Why MCC sizing matters
An undersized MCC busbar or starter will nuisance-trip or, worse, fail to withstand a downstream short circuit; an oversized one wastes capital. The three calculations every specifier must perform are:
- Motor full-load current (FLC) — sets the minimum rating of the contactor, overload relay, and feeder cable.
- Starting current — determines inrush withstand, voltage-dip impact, and the choice of starting method (DOL, star-delta, soft starter, or VFD).
- Prospective short-circuit current at the MCC busbar — sets the required breaking/withstand rating of the incomer and feeder devices, coordinated with the upstream transformer and protection relay settings (see our protection relay guide for relay coordination basics).

The method / formula
Three-phase motor full-load current:
I_FLC = P / (√3 × V × PF × η)
Where P = motor shaft output power (W), V = line voltage (V), PF = power factor, η = efficiency.
Starting current is expressed as a multiple of FLC, depending on the starting method:
I_start = k × I_FLC
Prospective short-circuit current at a busbar fed through a transformer of known impedance:
I_rated(transformer) = S / (√3 × V) I_sc ≈ I_rated / Z%
After-diversity demand current for an MCC with multiple feeders:
I_demand = (Σ I_FLC,i) × Diversity Factor
These four formulas are sufficient to size an MCC’s feeder devices, incomer breaker, busbar, and required short-circuit rating before detailed vendor engineering begins.
Worked example with computed numbers
Step 1 — Motor FLC. For a 160 kW, 400 V three-phase motor with an assumed efficiency of 0.94 and power factor of 0.87:
I_FLC = 160,000 / (1.732 × 400 × 0.87 × 0.94) ≈ 160,000 / 566.6 ≈ 282.4 A
The feeder contactor, overload relay, and cable must each be rated at or above this value, with the overload relay typically set at roughly 1.15 × FLC ≈ 325 A to allow for normal service tolerance while still tripping on sustained overload.
Step 2 — Starting current. For a direct-on-line (DOL) start with an illustrative starting multiplier of 6 × FLC:
I_start = 6 × 282.4 ≈ 1,694 A
This inrush, even if brief, must be checked against upstream voltage-dip limits and against the withstand rating of the contactor and busbar during the starting transient. If the dip is unacceptable, the designer substitutes a star-delta starter (illustrative multiplier ≈ 2–3 × FLC) or a soft starter/VFD (illustrative multiplier below 2 × FLC) to reduce the inrush.
Step 3 — Short-circuit level at the MCC busbar. For a 1000 kVA transformer at 400 V with a nameplate impedance of 5%:
I_rated = 1,000,000 / (1.732 × 400) ≈ 1,443.4 A I_sc ≈ 1,443.4 / 0.05 ≈ 28,868 A ≈ 28.9 kA
The MCC incomer and busbar must therefore be specified with a short-circuit withstand/breaking rating equal to or greater than this computed prospective fault current, coordinated with the upstream transformer protection and the MCC’s own feeder breakers.
Step 4 — Busbar sizing with diversity. Suppose the MCC serves six motor feeders with a combined connected FLC of 1,200 A. Applying an illustrative diversity factor of 0.75 (not all motors run simultaneously at full load):
I_demand = 1,200 × 0.75 = 900 A
The incomer and main busbar would then be selected at the next standard rating above 900 A (e.g., 1,000 A), rather than at the full connected load of 1,200 A — avoiding unnecessary oversizing while retaining margin for future feeders.
Selection / comparison table
| Parameter | DOL starter | Star-delta starter | Soft starter | Variable frequency drive (VFD) |
|---|---|---|---|---|
| Illustrative starting current multiplier | ~6–8 × FLC | ~2–3 × FLC | ~2–4 × FLC | <1.5 × FLC |
| Starting torque control | None | Stepped (transition bump) | Smooth ramp | Fully adjustable |
| Typical use case | Small/medium motors, strong supply | Medium motors, moderate supply stiffness | Pumps, fans, conveyors needing soft start/stop | Variable-speed process control |
| Relative panel space | Lowest | Low–medium | Medium | Highest |
| Harmonics on supply | Negligible | Negligible | Low | Requires filtering consideration |
Figures above are illustrative engineering ranges for comparative teaching purposes, not ratings of any specific product.
Selection criteria & common pitfalls
- Voltage class. Most MCCs operate at low voltage (≤1 kV) for motors up to a few hundred kW; large motors (several MW, typically above 1 kV) are switched via medium-voltage motor control centers using vacuum contactors or circuit breakers instead of LV contactors.
- Form of internal separation. IEC 61439-2 defines Forms of separation (barriers between busbar, functional units, and terminals) — higher Forms improve personnel safety and limit fault propagation between feeders but increase cost and footprint.
- Short-circuit withstand coordination. The MCC’s rated short-circuit withstand must be checked against the computed prospective fault current at its busbar (see worked example above), not assumed from a catalogue default.
- Starting method vs. supply stiffness. DOL starting is simplest but produces the highest inrush and voltage dip; weak or long-feeder supplies may force a soft starter or VFD even for modest motor sizes.
- Diversity and spare capacity. Sizing the incomer strictly off connected load (sum of FLCs) rather than after-diversity demand leads to oversized, costlier incomers; conversely, ignoring future motor additions leaves no spare feeder space.
- Enclosure and ingress protection. In dusty, high-humidity, or coastal environments common across the Gulf, North Africa, and Sub-Saharan Africa, enclosure IP rating and internal climate control (heaters, filtered ventilation) should be reviewed against IEC 60529 ingress classes.
- Overload and protection relay coordination. Overload relay and feeder breaker settings must coordinate with upstream protection relays and transformer fuses — see our protection relay guide for coordination fundamentals, and our switchgear hub for broader distribution-level coordination.
Standards
Motor control centers and their components are governed primarily by:
- IEC 61439-1 and IEC 61439-2 — general rules and particular requirements for low-voltage switchgear and controlgear assemblies, covering Forms of separation, temperature rise, and verification of assemblies such as MCCs.
- IEC 60947-4-1 — requirements for contactors and motor-starters, including overload relay coordination categories.
- IEC 62271-106 — requirements for high-voltage alternating-current contactors, relevant to medium-voltage motor control centers switching large motors.
- IEC 60529 — degrees of protection (IP codes) for enclosures.
Where a project specifies a different or national standard (e.g., an equivalent NEMA ICS framework), the underlying sizing calculations shown above remain the same; only verification and test procedures differ.
Related guides
See also our guides on medium voltage switchgear, gas-insulated switchgear and ring main units.
What is the difference between an MCC and a switchgear lineup?
A switchgear lineup typically distributes power to outgoing feeders (cables, transformers, other panels), while an MCC is purpose-built around motor starting and protection, combining isolators, starters/contactors, and overload devices for multiple motor feeders in one assembly.
How do I choose between a soft starter and a VFD?
Choose a soft starter when only a smooth start/stop is needed without continuous speed control; choose a VFD when the process requires variable speed operation, energy savings at part load, or precise torque/speed control throughout the run cycle.
Why does the overload relay setting differ from the motor FLC?
The overload relay is normally set slightly above the calculated FLC (commonly around 1.1–1.2 times FLC) to accommodate normal service tolerances while still tripping reliably on a genuine sustained overload condition.
What causes an MCC busbar to be undersized in practice?
The most common cause is sizing the incomer and busbar from the raw sum of connected motor FLCs without applying a diversity factor, or failing to recompute the prospective short-circuit current after a transformer upgrade.
Is a medium-voltage MCC different from a low-voltage MCC?
Yes — low-voltage MCCs use contactors and circuit breakers for motors below roughly 1 kV, while medium-voltage MCCs use vacuum contactors or MV circuit breakers for large motors operating above 1 kV, with different insulation and arc-management requirements.
How does ambient temperature affect MCC sizing in hot climates?
High ambient temperatures reduce the current-carrying capacity of busbars, cables, and contactors, so derating factors must be applied in Gulf, North African, and Sub-Saharan African installations where enclosure internal temperatures can exceed temperate-climate design assumptions.
Which IEC standard should I ask a vendor to certify an MCC against?
Request compliance verification to IEC 61439-1/61439-2 for the assembly itself, and IEC 60947-4-1 for the individual contactors and motor-starters installed within it.